Siemens Circuit Breaker 3RV1011-0AA15
Type: Circuit Breaker
Brand: Siemens
Type | 3RV1 |
Breaker Type | Motor Protection Circuit Breakers |
Rated current | 0.16 |
Number of Poles | 1 pole |
Setting range for thermal overload releases | 0.11...0.16 A |
Suitable for induction motors with P | 0.04 kW |
Instantaneous overcurrent releases | 2.1 A |
Short-circuit breaking capacity | 100 kA |
Weight approx. | 0.245 kg |
product brand name SIRIUS
product designationCircuit breaker
design of the productFor motor protection
product type designation3RV1
General technical data
size of the circuit-breakerS00
size of contactor can be combined company-specific S00
product extension auxiliary switch Yes
power loss W for rated value of the current
at AC in hot operating state5.5 W
at AC in hot operating state per pole1.8 W
insulation voltage with degree of pollution 3 at AC rated value690 V
surge voltage resistance rated value 6 kV
maximum permissible voltage for safe isolation in networks
with grounded star point betweenmain and auxiliary circuit 400V
protection class IP on the front IP20 of the termina lIP00
mechanical service life (switching cycles)
of the main contacts typical 100 000
of auxiliary contacts typical100 000
electrical endurance (switching cycles) typical 100 000
reference code acc. to DIN EN 81346-2 Q
Ambient conditions
installation altitude at height above sea levelmaximum 2 000 mambient temperature
during operation-20 - +60 degrees centigrade
during storage-50 - +80 degrees centigrade
during transport-50 - +80 degrees centigrade
temperature compensation-20 - +60 degrees centigrade
relative humidity during operation10 - 95 %
Main circuit
number of poles for main current circuit 3
adjustable pick-up value current of the current-dependent overload release0.11 - 0.16 A
operating voltage rated value690 V at AC-3 rated value maximum 690 V
operating frequency rated value50 - 60 Hz
operating current rated value 0.16 A
operating current
at AC-3
at 400 V rated value 0.16 A
operating power
at AC-3v at 230 V rated value25 W
at 400 V rated value40 W
at 500 V rated value60 W
at 690 V rated value60 Woperating frequency
at AC-3 maximum15 1/h
design of the auxiliary switch transverse
number of NC contacts for auxiliary contacts 1 note 1
number of NO contacts for auxiliary contacts 1 note 1
number of CO contacts for auxiliary contacts 0
operating current of auxiliary contacts at AC-15 at 24 V 2A at 110 V 2A at 120 V 2A at 125 V 2A at 230 V 0.5A
operating current of auxiliary contacts at DC-13 at 24 V 1A at 60 V 0.15A
Protective and monitoring functions
product function ground fault detection No phase failure detection Yes
trip class CLASS 10
design of the overload release thermal
operational short-circuit current breaking capacity(Ics) at AC
at 240 V rated value 100 kA
at 400 V rated value 100 kA
at 500 V rated value 100 kA
690 V rated value 100 kA
maximum short-circuit current breaking capacity (Icu)
at AC at 240 V rated value 100 kA
at AC at 400 V rated value 100 kA
at AC at 500 V rated value 100 kA
at AC at 690 V rated value 100 kA
response value current of instantaneous short-circuit trip unit 2.1 A
UL/CSA ratings
full-load current (FLA) for three-phase AC motor
at 480 V rated value 0.16 A
at 600 V rated value 0.16 A
contact rating of auxiliary contacts according to ULC300 / R300
Short-circuit protection
product function short circuit protection Yes
design of the short-circuit tripmagnetic
design of the fuse link
for short-circuit protection of the auxiliary switch required
fuse gG: 10 A, miniature circuit breaker C 6 A (short-circuit currentIk < 400 A)
design of the fuse link for IT network for short-circuitprotection of the main circuit
at 240 V none required
at 400 V None required
at 500 V None required
at 690 V None required
Installation/ mounting/ dimensions
mounting position any
mounting type screw and snap-on mounting onto 35 mm standard mounting railaccording to DIN EN 60715
height 90 mm width 45 mm depth 75 mm