All controllers of XR500 series can be connected to XWEB remote through two terminals of RS485 interface.
process monitoring system.
The external dimension of XR570C is 32×74mm, it is used for medium and low temperature refrigeration system, controller
Three-way relay output is used to control compressor, defrost (electrical defrost or hot gas defrost) and
Evaporator fan, there are also relays that can be used for alarm or auxiliary output. Two PT1000
or NTC sensor input, one for temperature control and one for evaporator control
Defrost termination temperature, two digital inputs (passive contacts) can be set by parameters for their functions
Yes, built-in buzzer alarm. Parameters can be set through the keys on the control panel, easily
realize various functions.
3. Load Control
3.1 Compressor Control
English description in the figure: Temper.: Temperature axis; Time: Time axis; Compr.: Compressor; ON: On
machine.
The principle of adjusting the temperature is to add a positive temperature difference Hy to the set value of the room temperature Set, and the room temperature sensor
When the detected temperature of the detector rises to Set+Hy, the compressor starts, and when it returns to the Set value
, the compressor stops running.
If the temperature sensor fails, the compressor start and stop times are determined by COn and COF
The parameter implements timing start and stop control.
3.2 Quick freezing
That is, when the compressor does not stop and does not defrost, it keeps pulling the temperature: press the key to hold
It can enter the quick cooling state for about 3 seconds; set the compressor quick cooling cycle through the CCt parameter,
To end, press the key again for three seconds.
3.3 Defrost
There are three defrosting methods that can be set through the "tdF" parameter: electric defrosting (tdF=rE), hot air defrosting
Frost (tdF=in), temperature-controlled defrost (tdF=rt). The defrosting interval is controlled by the "EdF" parameter.
Number setting, when EdF=in, defrost every time interval set by “IdF”, EdF=Sd
is the smart defrost type when the compressor is running and the evaporator temperature is below "SdF"
The time at the temperature set by the parameter is accumulated into the defrost interval "IdF".
The dripping time at the end of defrosting is set by the "Fdt" parameter.
3.4 Evaporator Fan Control
The fan operation mode is selected by the FnC parameter:
FnC=C-n Fan and compressor start and stop at the same time, and stop when defrosting;
FnC= O-n The fan keeps working and stops when defrosting;
FnC= C-y The fan and the compressor start and stop at the same time, and work during defrosting;
FnC=O-y The fan works continuously, even when defrosting.
The drain time after defrosting is set by the Fnd parameter, during which the fan stops.
When the temperature detected by the evaporator probe is higher than the temperature set by the parameter "FSt", the fan is always turned off
close. When the temperature is lower than the temperature set by "FSt", the air circulation in the warehouse is allowed.
4. Control Panel
SET : Display and modify the current set value. During the parameter setting process, select the parameter or
Confirm the operation.
Press this key for 5 seconds to activate the standby function (if allowed by parameter settings).
Press this key for 3 seconds, when the stored maximum or minimum temperature is displayed
Used to clear history.
: Press and hold for 3 seconds to start manual defrost (provided that defrost conditions allow).
: Up key to view the maximum temperature; in the parameter setting state, you can browse down the parameter code
code or increase the parameter value. Press and hold this key for 3 seconds to activate the quick cooling function.
: Down key Down key View the minimum temperature. In the parameter setting state,
Parameter codes can be browsed up or the parameter value can be decreased. Press and hold this key for 3 seconds to assist
The relay is open or closed (can be set).
Group
Ask questions
(0/1,200)
Max 1200 characters
Q: How can I unsubscribe from marketing emails?
A: To unsubscribe from marketing emails, you can click on the "Unsubscribe" link located at the bottom of the email. This will allow you to opt out of receiving further marketing communications from us.
Q: How can I compare prices and reviews of similar products?
A: On the product list page, you can view the prices and ratings of different items simultaneously. You can also use filters to sort products by price or rating, facilitating your comparison and selection.
Q: How can I participate in promotions or giveaways organized by sellers?
A: We regularly hold promotional events and organize giveaways and gift activities. You can follow our official announcements, emails, or social media channels to get information on how to participate and the details of these activities.
View More
Question has been sent successfully
Reviews
P
Pamela Elkington
Dec 29, 2024
Dixell Temperature Controller XR570C
Good price and delivered as promised.
Helpful
Unhelpful
D
D.I Mouro
Sep 19, 2024
Dixell Temperature Controller XR570C
The process was smooth, and I’ll definitely purchase from this company again. The material arrived ahead of schedule. Thanks!