Causes and troubleshooting of industrial chillers
1. High condensing pressure (higher than the specified value) failure causes and remedies:
①There is non-condensable gas in the system: release non-condensable gas.
②The chiller has insufficient cooling water and the water temperature is too high: check if the water valve is open and the water filter is blocked, try to lower the water temperature.
③ There is dirt in the condenser that affects the heat transfer area: clean the condenser.
④ Too much liquid in the condenser: release excess refrigerant.
2. Compressor suction pressure is too low failure causes and remedies:
①Liquid throttle valve or suction filter is blocked: disassemble, inspect and clean.
② Insufficient refrigerant in the system: replenish refrigerant.
③ Insufficient refrigerant in the evaporator: open a large throttle.
④There is too much oil in the system: find the oil-collecting part of the system and release the oil.
3. The chiller compressor stops shortly after it starts. Causes and remedies:
①The oil pressure is too low: Use the oil pressure regulating valve to increase the oil pressure. If it cannot be increased, check and repair according to the serial number 6.
②The setting value of the oil pressure difference relay is too high: re-adjust.
4. Compressor discharge temperature relative to pressure drop and high temperature failure causes and remedies:
①The temperature of the inhaled gas is too high: Check and adjust according to the serial number 5.10.
②The exhaust valve is broken: Open the cylinder head to check the valve.
③Safety valve leakage: check the safety valve for adjustment and repair.
④ Piston ring leakage: check, repair or replace.
⑤ The gasket under the cylinder liner is broken and leaking: check and replace.
5. Reasons and remedies for compressor failure to start:
① Gas line failure: check and repair.
②The differential pressure relay is disconnected, and the high-voltage circuit breaker is disconnected: press the reset button of the differential pressure relay and wait for the pressure change to
The contact is closed or the opening pressure is readjusted.
6. Remedy for insufficient refrigeration capacity:
①The position of the spool valve is inappropriate or other failures: check the indicator and adjust the position to repair the spool valve.
②The suction filter is blocked, the suction pressure loss is too large, the suction pressure drops, and the volumetric efficiency is reduced: remove the filter screen of the suction filter and clean it.
③ Abnormal wear and tear of the machine causes excessive gaps: adjust or replace parts.
④The suction pressure is lower than the evaporation pressure. Check the valve (such as suction stop valve or check valve, etc.)
⑤ Leakage between high and low pressure systems; check the bypass pipelines used for driving and stopping.
⑥Insufficient fuel injection volume can not achieve the sealing effect: check whether the safety valve is sealed, check the oil circuit, oil pump, and oil filter to increase the oil volume.
⑦The exhaust pressure of the machine is much higher than the condensing pressure, and the volumetric efficiency is reduced: check the exhaust system pipes and valves, and remove the resistance of the exhaust system. If air leaks into the system, it should be eliminated.
Seven. The compressor suction temperature is higher than the evaporating temperature (higher than the specified value). Causes and remedies:
① Insufficient refrigerant in the system: replenish refrigerant.
② Insufficient refrigerant in the evaporator: open a large throttle.
③The water content exceeds the regulation: check the water content.
④The low-pressure pipe insulation of the refrigeration system is not good: check and repair.
8. Compressor unloading device mechanism failure causes and remedies:
①Insufficient oil pressure: Adjust the oil pressure to be 0.15-0.2Mpa higher than the suction pressure.
②The oil pipe is blocked: disassemble and clean.
③ There is dirt stuck in the cylinder: disassemble and clean.
Nine. How to troubleshoot abnormal noise during machine operation:
①There are sundries in the rotor tooth slots: check the rotor and suction filter.
②The thrust bearing is damaged: replace it.
③The friction between the rotor and the casing caused by bearing wear: replace the main bearing.
④Spool valve deflection: repair the spool valve guide block and guide post.
⑤ Loose joints of moving parts: disassemble the machine for maintenance and strengthen anti-loosening measures.
Causes and troubleshooting of industrial chillers
Recent related posts
-
07/30/2020
Causes and troubleshooting of industrial chillers
1. High condensing pressure (higher than the specified value) failure causes and remedies:<br></br> ①There is non-condensable gas in the system: release non-condensable gas.
-
07/30/2020
Why is the opportunity for low-temperature industrial cold water slow
When it comes to low-temperature industrial chiller equipment, many friends may know that low-temperature industrial chiller products are a type of professional refrigeration equipment widely used in domestic industrial production.
-
07/30/2020
6 steps to maintain industrial chiller equipment
Preventive maintenance has the potential to make your heating and air-conditioning systems operate reliably and efficiently. You may not realize that regular maintenance is equally important to your industrial chiller.
-
07/30/2020
Case analysis of maintenance of central air-conditioning compressor
We all know that the compressor is the heart of the refrigeration system, and it can be said to be the lifeblood of the refrigeration system. The compressor often has various problems during long-term use.
-
07/30/2020
What should I do before the air conditioner is turned on for the first time when I encounter the new crown virus in summer?
In a live broadcast last night, Dr. Zhang Wenhong stated that China’s epidemic prevention and control has done a good job. When people wear masks, the probability of contracting the new crown virus is very small.
-
07/30/2020
What are the common faults of refrigerators?
Freezers are an indispensable piece of household appliances. After long-term use, more or less problems will occur.
-
07/30/2020
Common faults and solutions of summer chillers
Entering the hot summer, industrial chillers in many factories ushered in the peak period of refrigeration. The refrigeration equipment frequently runs, and it is very likely that there will be such and other small failures.
-
07/29/2020
8 standard processes for central air-conditioning installation, let you become an expert from a rookie~
In terms of home improvement, concealed projects include water and electricity, as well as central air-conditioning. Central air-conditioning has three points of quality and seven points of installation; there are many kinds of materials and technology for installation
-
07/29/2020
Briefly talk about scroll, screw, piston, centrifugal refrigeration compressor Piston refrigeration compressor
Piston refrigeration compressor<br></br> Piston type (ie, reciprocating) refrigeration compressors are widely used, but the displacement is not large. Generally, they are small and medium-sized compressors. The cooling capacity of general air-conditioning conditions is less than 300kW.
-
07/29/2020
Refrigerant filling
After the leak test of the refrigeration system is completed, it should be filled with refrigerant. However, the Freon refrigeration system must be vacuum dried before being filled with refrigerant. When the drying is not complete, the refrigerant cannot be filled.
Customers frequently viewed
IWAYA DENKI Water Pump 25CJT0752
Panasonic Servo Motor MHMF022L1V2M
Honeywell Solenoid Valve VE4025B1045
ROTEN Mechanical Seal 8E5K-22-X
Sanyo Capacitor 4V 1200UF 10X12
Rockwell A-B Sensor 42FB-F2LPA-A2
Ebmpapst Fan R3G225-8317075812