Selection requirements for refrigeration piping parts of chillers
The accessories of the refrigeration pipeline of the chiller mainly include various valves and connectors. According to different refrigeration systems, chillers have different requirements for piping accessories. If the refrigeration piping accessories are selected incorrectly, or the installation does not meet the requirements, it will directly affect the cooling effect of the chiller.
One, valve
Various valves should adopt special products that conform to the refrigerant. The valves used in the ammonia system chiller should meet the following requirements:
1. The valve body is gray cast iron, temperable iron or cast steel. The strength test pressure is 29~39bar, and the tightness test pressure is 19~25bar. Generally, a valve with a nominal pressure of 24.5 bar can meet the requirements.
2. The valves used in the ammonia system chiller are not allowed to have copper, galvanized, and tin-plated parts.
3. The valve should have a reverse valve seat, and the packing can be replaced during operation when the valve is fully opened.
Ⅱ、Connector
Ammonia system chiller pipes are mainly welded, and those with a pipe wall thickness of less than 4mm use gas welding, and those with a wall thickness of more than 4mm use electric welding. Flanges can also be used where necessary, and single flanges should have concave and convex openings; all elbows should be simmered; The valve and pipe thread connection must not use white oil hemp wire, and should use pure pure glycerin and yellow powder blended packing; when the branch pipe is connected to the header box, the branch pipe should be connected with the header with an arc-shaped fork to avoid mismatching liquid Evenly.
In the Freon refrigeration system, its connection method is: steel pipe and steel pipe are welded, steel pipe and copper pipe are silver welded, copper pipe and copper pipe are silver welded, and the pipe wall should not be galvanized, and the flange should not be used with natural rubber , Mineral oil is not allowed, and its sealing material should be corrosion-resistant material, generally nitrile rubber.

Related Info
Poor heat dissipation of screw chiller and its treatment Popularization of food cold storage and precautions for use Precautions for the use of refrigerated trucks Precautions when the FRP cooling tower is assembled and ready for operation Reasons for water leakage of air conditioner in computer room and common treatment methodsSelection requirements for refrigeration piping parts of chillers
Subscribe to relevant news content?
Subscription
Unsubscription
Recent related posts
Customers frequently viewed
IWAYA DENKI Water Pump 25CJT0752
US$2307.69
Panasonic Servo Motor MHMF022L1V2M
US$653.85
Honeywell Solenoid Valve VE4025B1045
US$334.62
ROTEN Mechanical Seal 8E5K-22-X
US$384.62
Eaton Moeller Circuit Breaker LZMN1-A25
US$207.72
Autonics Rotary Encoder E40HB6-2-4-V-24
US$1153.85
ULVAC Vacuum Pump PMB600DT-MF9A1R4I2B1
Contact Us
LEEMIN Filter XU-160-100-J
US$168.08
Toshiba Compressor FE30CHR
Contact Us
Honeywell Expansion Valve TLEX-E0743
Contact Us
Caddock Resistor MP850-400-5%
US$1.35
Bristol Compressor H24B263ABCX
Contact Us