System handling guide after the refrigeration compressor is damaged
The refrigeration compressor in the refrigeration system cannot be directly replaced with a new compressor after it is damaged, because there may be some incentives for the refrigeration compressor to be damaged in the system, and the new compressor must be replaced after all the incentives are eliminated.
1. After removing the original damaged refrigeration compressor, the system must be purged with nitrogen before connecting the new refrigeration compressor system.
2. During the welding operation, in order not to form an oxide film on the inner wall of the copper pipe, nitrogen must be introduced, and the time for the nitrogen must be sufficient.
3. It is forbidden to use the compressor as a vacuum pump to evacuate the air in the pipeline of the external machine when replacing the refrigeration compressor or other parts, otherwise the compressor will be burned and a vacuum pump must be used to vacuum.
4. When replacing the refrigeration compressor, an appropriate amount of refrigerating oil must be added to the compressor.
5. The cause of damage to the original compressor must be checked before replacement, and defective parts must be replaced. Because the damage of other components will directly cause damage to the compressor.
6. When replacing the refrigeration compressor, the filter drier must be replaced in time. Because the desiccant in the filter drier has been saturated, the water filtering function is lost.
7. The refrigerating oil in the original system must be cleaned, because the new pump has been injected with sufficient mass-produced refrigerating oil. Different brands of refrigerating oil cannot be mixed, otherwise it will deteriorate and cause poor lubrication, causing the refrigeration compressor to pull the cylinder and turn yellow , Burnt.
8. When replacing the refrigeration compressor, pay attention to prevent excessive refrigeration oil in the system, otherwise it will cause the heat exchange effect of the system to decrease, thereby making the system pressure higher and damaging the system and the compressor.
9. Do not fill the refrigerant too fast, otherwise it will cause liquid hammer, which will cause the valve plate to break and cause the compressor to lose pressure.
10. After installation, check whether the radiator is working properly. If the system pressure exceeds the normal pressure (13-15kg), it will cause the clutch to slip, bearings, coils, or compressor damage.
System handling guide after the refrigeration compressor is damaged
Recent related posts
-
08/05/2020
System handling guide after the refrigeration compressor is damaged
The refrigeration compressor in the refrigeration system cannot be directly replaced with a new compressor after it is damaged, because there may be some incentives for the refrigeration compressor to be damaged in the system
-
08/05/2020
Simple estimation and measurement of indoor and outdoor wind pressure difference in fresh air system
At present, most of the fresh air systems we use follow the design philosophy of large air volume and slight positive pressure, but many people are also confused about this. How to detect the pressure in the room on site?
-
08/05/2020
Selection skills of precision air conditioner and comfort air conditioner
When doing intelligent and informatized projects, it is inevitable to do computer room projects. Air-conditioning is inevitable for computer room engineering. Some people will say that the cost of precision air-conditioning is so high.
-
08/05/2020
Refrigeration oil replacement points of screw refrigeration compressors for cold storage equipment
1. The role of lubricating oil:<br></br> 1) A dynamic seal is formed between the screw and the compression chamber and the male and female screws to reduce the leakage of refrigerant from the high pressure side to the low pressure side during the compression process.<br></br>
-
08/05/2020
Problems of evaporator defrosting and improvement methods
Although the evaporator is very useful, the evaporator defrosting electric heating tube burned out and the water collecting tray heating chamber burned out successively during use. So I will introduce the problems of the evaporator equipment and analyze the problems.
-
08/05/2020
Power saving is the last word! Read energy efficiency labels in one minute
With the improvement of living standards, household central air conditioners have gradually become the new darling of modern families.
-
08/05/2020
Issues that need attention when moving air conditioners
1. Preliminary preparation At least two or more skilled refrigeration repairmen, a set of tools, safety belts and other safety equipment.
-
08/05/2020
How to solve the problem of too high compression ratio of chiller
In the process of using industrial chillers, various problems will inevitably occur. Due to the structure of the industrial chiller, once the compression ratio of the compressor is too high, it will affect the working efficiency of the industrial chiller.
-
08/05/2020
How to solve the common old problems in the operation of chillers
In the pharmaceutical, food, chemical and other industries, process water cooling is required. The chiller has become a must-choice equipment for many industries.
-
08/05/2020
How to choose the distance between cold storage air coolers
As the evaporator commonly used in the refrigeration system, the air cooler directly affects the efficiency of the refrigeration system. As we all know, the air cooler will use different fin spacings according to the required ambient temperature.
Customers frequently viewed
IWAYA DENKI Water Pump 25CJT0752
Panasonic Servo Motor MHMF022L1V2M
Honeywell Solenoid Valve VE4025B1045
ROTEN Mechanical Seal 8E5K-22-X
EMERSON Power Supply UL33-0300L
Panasonic Relay DSP1a-DC5V
Autonics Switch S3PF-P3BABD
Omron PLC CP1L-L20DT1-D
Panasonic Servo Motor MDME304SCH