How to reduce the discharge temperature of refrigeration compressor
The refrigeration compressor is the core and heart of the refrigeration system. The capacity and characteristics of the compressor lead to the capacity and characteristics of the refrigeration system. In a sense, the design and matching of the refrigeration system is to reflect the capacity of the compressor.
1. Reduce the intake air temperature
The intake air temperature at all levels is related to the cooling imperfection of the intercooler, so we should try our best to ensure the cooling effect of the intercooler, or adopt some special cooling measures to reduce the intake air temperature and strive to reduce the exhaust temperature.
Two air intake in the cylinder
In compressor maintenance, attention should be paid to the installation of valves and the selection of springs. On the premise of ensuring the normal operation of the valves, the pressure loss of inlet and outlet should be minimized to achieve the purpose of reducing the exhaust temperature.
Third, the compression process index will also affect the exhaust temperature
In actual operation, the compression process index is mainly related to the cylinder cooling condition. The better the cooling effect and the smaller the index, the lower the exhaust temperature. Therefore, the cooling of the cylinder can be enhanced to reduce the exhaust gas temperature.
Fourth, internal leakage is one of the most important reasons for the high or even high exhaust temperature
Practice has shown that internal leakage is one of the most important reasons for high or even high exhaust temperature. Especially in the expansion and suction process of a certain stage of the compressor, if the exhaust valve of that stage is not closed tightly, the high temperature and high pressure gas in the exhaust pipe that can be cooled in the future will return to the cylinder (internal leakage), which will cause the stage to exhaust. The temperature rose sharply. For this reason, special attention should be paid to prevent such situations from happening.
5. For multi-stage compressors, it is often not a single situation to adjust or reduce the exhaust temperature of a certain stage
For example, if the exhaust temperature of a certain stage is found to be relatively high, if the method of adjusting (increasing) the clearance volume is used, the pressure ratio of the stage is appropriately reduced, so that although the exhaust temperature of the stage can be reduced, it will make the front The pressure ratio of the first stage increases, and the exhaust temperature rises; if an attempt is made to reduce the exhaust temperature by strengthening the cooling of the cylinder of this stage and reducing the compression process index, it will also cause the pressure ratio of this stage to drop and the pressure ratio of the next stage to increase. When the cooling effect of the intercooler before this stage is strengthened, the exhaust temperature can be reduced by reducing the intake air temperature, but the intake pressure of this stage is also reduced accordingly. Increase the pressure ratio of this stage, so the effect of reducing the exhaust temperature is not obvious. Therefore, it is necessary to adopt a comprehensive method, for example, while strengthening the cooling before the stage, and appropriately increasing the clearance volume of the stage to keep the pressure ratio of the stage unchanged, not only can the exhaust temperature of the stage be effectively reduced, but also it will not be affected. The exhaust temperature of the front and rear stages.

Related Info
Does car air conditioner cost oil for cooling or heating? Do you really know? The working principle of cooling and heating of air conditioning Carrier screw compressor motor repair Ford Explorer air conditioner fails to refrigerate troubleshooting Method for identifying failure of hermetic refrigeration compressorHow to reduce the discharge temperature of refrigeration compressor
Subscribe to relevant news content?
Subscription
Unsubscription
Recent related posts
Customers frequently viewed
IWAYA DENKI Water Pump 25CJT0752
US$2307.69
Panasonic Servo Motor MHMF022L1V2M
US$653.85
Honeywell Solenoid Valve VE4025B1045
US$334.62
ROTEN Mechanical Seal 8E5K-22-X
US$384.62
HENGSTLER Encoder RI76TD/1024ED.1A20KF
US$587.84
BANLMEYD BMD Bearing GE35ES-2RS
US$30.38
Copeland Compressor 4DR1-3000-FSD-200
Contact Us
IKO Linear Guideway LWE30R760SLS1
US$789.28
LUT Bearing F16004-ZZ
US$0.97
SKF Bearing 22256 CCK/W33
US$4615.38
IMI Norgren Solenoid Valve V04A286M-Q116A
Contact Us
Danfoss Compressor MTZ19JA1VE
US$4499.10