How to replace the lubricating oil and filter drier of the chiller
After the chiller is used for a long time, the lubricating oil will inevitably be contaminated or acidified. Therefore, we must pay attention to the change of oil quality during the operation of the unit. While changing the lubricating oil, check whether the filter drier is blocked and replace it. So, what the editor of okmarts.com shared with you today is how to replace the lubricating oil and filter drier of the chiller.
1. Preparation
Check whether the compressor lubricating oil has been preheated for more than 8 hours. Before the test run, the oil heater is energized and heated for at least 8 hours to prevent the refrigerating oil from foaming during startup. If the ambient temperature is low, the oil heating time needs to be relatively longer. When starting at a low temperature, due to the high viscosity of the lubricating oil, there will be situations such as difficulty in starting and poor loading and unloading of the compressor. Generally, the lubricating oil temperature z* needs to be above 23℃ to run the chiller. Start the machine, record the operating parameters and analyze the existing and current problems of the machine, and make preparations.
1. Short-circuit the high and low pressure difference switch. (It is better not to adjust the pressure difference switch. You can short the two wires directly.) When the machine is running at full load (100%), close the angle valve. (Pay special attention to the recovery of the differential pressure switch after the refrigerant is recovered)
2. Press the emergency switch or turn off the power when the low pressure pressure of the chiller is less than 0.1MP. Since there is a one-way valve at the compressor exhaust port, the refrigerant will not flow back to the compressor, but sometimes the one-way valve may not close tightly, so it is best to turn off the compressor exhaust when pressing the emergency switch valve.
2. When the above work is completed, turn off the main power supply and proceed to the following process:
1. Drain the oil. The freezing oil sprays out quickly under the pressure of the system refrigerant gas. Take care not to spray outside. Drain the refrigerant while draining the oil, and open the high pressure gauge shut-off valve.
2. Clean the oil tank and the oil filter, open the oil tank cover, clean the oil tank with dry gauze, throw the waste refrigerating oil into the gauze when the gauze is dirty, take out the two magnets in the oil tank, clean it, and put it back into the oil tank. Disassemble the oil filter with a large wrench and clean it with waste oil.
3. Replace the filter drier:
A) There are 3 filter elements of the filter drier, and the replacement speed should be fast to prevent too long contact with the air to absorb excessive moisture.
B) The filter is packaged in a can, so pay attention to protection during transportation. Once the package is found to be damaged, it will be invalid.
3. Vacuum and refuel
According to the structure of the industrial chiller compressor, it is best to refuel from the high pressure side. Because the compressor's high-pressure and low-pressure chambers are not directly connected, it is difficult to return the oil from the low pressure to the oil tank. Generally, we use a vacuum method to evacuate oil from the low-pressure side to suck in the oil from the high-pressure side.
Refueling the blind pipe: Replenish the blind pipe with the replaced waste refrigeration oil.
Four, warm-up:
Power-on preheating and at least heat the oil to a temperature above 23°C before it can start up.
water chillers include box-type air-cooled chillers/water-cooled chillers, screw chillers, open chillers, and low-temperature chillers. The structure of each type of chiller is different. If the chiller needs maintenance or repair, you must find the chiller manufacturer, who has a free one-year warranty service, or find a more professional repair point near the factory. Do not disassemble the chiller privately. operating.

Related Info
How to choose the internal machine for cold storage Choose air cooler or exhaust pipe How to deal with the high pressure overload of the chiller How to install large-scale cold storage refrigeration equipment How to install the cold storage air curtain How much do you know about these technologies How to judge the chilled water flow of the chillerHow to replace the lubricating oil and filter drier of the chiller
Subscribe to relevant news content?
Subscription
Unsubscription
Recent related posts
Customers frequently viewed
IWAYA DENKI Water Pump 25CJT0752
US$2307.69
Panasonic Servo Motor MHMF022L1V2M
US$653.85
Honeywell Solenoid Valve VE4025B1045
US$334.62
ROTEN Mechanical Seal 8E5K-22-X
US$384.62
VBI Bearing 61921-2Z
US$65.38
HORIBA Conductivity Meter ES-71
US$3538.46
CKD Solenoid Valve 4F520-15-AC110V
US$340.38
Kuebler Encoder 8.5000.8122.5000
Contact Us
Parker Sporlan Expansion Valve 100467
Contact Us
Omron VFD Frequency Converter 3G3RX-A4900
Contact Us
Kollmorgen Servo Drive AKD-P00306-NBAN-0000
Contact Us