Precautions for safe operation of chiller
Water chiller is a kind of cooling water equipment that can provide constant temperature, constant current and constant pressure. The working principle of the chiller is to inject a certain amount of water into the water tank in the machine, and then the water is cooled by the chiller refrigeration system, and then the low-temperature cooling water is sent to the equipment to be cooled by the water pump, and the chilled water takes the heat away after the temperature It is raised and then returned to the water tank to achieve cooling. When using, you should pay attention to the following matters.
1. During installation, please check whether the machine is damaged, and choose a suitable place for installation and future maintenance.
2. The place where the unit is installed must be the floor, installation mat or foundation, whose levelness is within 6.4mm, and can bear the operating weight of the unit.
3. The unit should be placed in a room with a room temperature of 4.4-43.3°C, and there should be enough space around and above the unit for routine maintenance.
4. At one end of the unit, there should be a space for pipe extraction to clean the condenser tube bundle, and door openings or other suitable openings can also be used.
5. Select the water pipe with the appropriate pipe diameter, the cooling system and the cold water system when the unit is running at the maximum power, and connect them correctly.
6. For common applications, the water flow speed through the evaporator and condenser should be between 1.0-3.6m/s.
7. The water flow rate should remain stable under any load.
8. The design and installation of all chilled water and cooling water pipelines should be carried out according to conventional methods, and the chilled water pump should be located on the inlet pipe of the unit to ensure the positive pressure and flow in the unit. When piping, damping pipes should be installed to ensure proper flexibility, and to prevent water from the evaporator from being drained when the pump is stopped.
9. The pipeline should have a firm support independent of the chiller to avoid stress on the components of the chiller. The hanger should be set to facilitate pipe alignment.
10. In order to reduce noise and vibration, it is best to install vibration isolators on the pipeline.
11. In order to use the chiller economically and effectively, it is recommended to ask a water treatment expert to analyze the water quality of the evaporator and condenser. Poor water quality will cause fouling and affect heat transfer, or produce corrosion deposits, breed organic matter, and affect the performance of the unit. Increase operation and maintenance costs. Bus processing machine
12. Generally speaking, correct water treatment and regular cleaning of the tube bundle can maintain its good performance. If the existing water quality conditions cannot be improved by appropriate methods, then it is necessary to consider allowing the tube bundle to have a larger fouling coefficient or specify Specialized structural materials.
13. Please install a filter at the inlet of the water pipe and clean it regularly.
14. After the leak test is completed, all nozzles must be rust-proofed.
15. In order to facilitate daily maintenance work, the user can take some (or all) of the following measures:
- Pressure gauges and shut-off valves with plugs can be installed on the inlet and outlet pipes of cooling water and chilled water, as close as possible to the chiller;
- Hanging rails and beams can be erected above the equipment to facilitate maintenance.
When operating the chiller, please pay attention to the above matters. It will definitely benefit everyone.

Related Info
Normal operating conditions of the refrigeration system in operation Poor cooling equipment There is a foreign body at work! Popular science the advantages of water source heat pump central air-conditioning Power saving tips for air conditioners and refrigerators Precautions for cold storage installationPrecautions for safe operation of chiller
Subscribe to relevant news content?
Subscription
Unsubscription
Recent related posts
Customers frequently viewed
IWAYA DENKI Water Pump 25CJT0752
US$2307.69
Panasonic Servo Motor MHMF022L1V2M
US$653.85
Honeywell Solenoid Valve VE4025B1045
US$334.62
ROTEN Mechanical Seal 8E5K-22-X
US$384.62
SKF Bearing NN 3040 KTN9 P4
US$2330.77
Ebmpapst Fan G1G133-DE03-S01
Contact Us
Schneider Circuit Breaker LV430641
US$3000.00
DEREK Tool for Metal Cutting FP45 300-60
US$1576.92
Daikin Air Conditioner RUXYQ32AB
US$3423.08
CEWE Transmitter DP125
US$878.91
CHELIC Air Cylinder JGD63*85-B
US$240.38
HAVIS Tool for Metal Cutting SR0038M30
US$348.08