Type | SENTRON VL1250 |
Breaker Type | Sentron Molded Case Circuit Breakers |
Ampere Rating | 1250 A |
Interruption | High interruption |
Number of Poles | 3 pole |
circuit breaker VL1250H w/o Electronic Trip Unit high breaking
capacity Icu=70kA/415V AC, 3-pole In=< 1250A, rated current
without auxiliary release with screw terminal connections for
switching unit and ETU
Model
type of the driving mechanism / motor drive No
General technical data
number of poles 3
size of the circuit-breaker 3VL7
mechanical service life (switching cycles) / typical 3 000
electrical endurance (switching cycles) / typical 1 500
Current
continuous current / rated value 1 250 A
derating temperature / for the rated value of the
continuous current
50 degrees centigrade
acc. to UL 489 40 degrees centigrade
Main circuit
operating frequency
1 / rated value 50 Hz
2 / rated value 60 Hz
operational current
at 40 degrees centigrade / rated value 1 250 A
at 50 degrees centigrade / rated value 1 250 A
at 55 degrees centigrade / rated value 1 162 A
at 60 degrees centigrade / rated value 1 162 A
at 65 degrees centigrade / rated value 1 075 A
at 70 degrees centigrade / rated value 1 075 A
Short circuit
breaking capacity operating short-circuit current (Ics)
at 240 V / rated value 50 kA
at 415 V / rated value 35 kA
at 500 V / rated value 30 kA
at 690 V / rated value 15 kA
breaking capacity maximum short-circuit current (Icu)
at 240 V / rated value 100 kA
at 415 V / rated value 70 kA
at 440 V / rated value 50 kA
at 480 V / acc. to NEMA / rated value 50 kA
at 500 V / rated value 40 kA
at 600 V / acc. to NEMA / rated value 30 kA
at 690 V / rated value 30 kA