Analysis of common failure causes of hermetic refrigeration compressors
1. How to identify the 3 terminals on the casing of a hermetic compressor?
The resistance between running terminal (R), starting terminal (S), common terminal (C), RS is greater than the resistance between SC and RC. The resistance between RS is equal to the resistance between SC and the resistance between RC.
The above rules can be used to distinguish. It should be noted that the resistance value of the terminal temperature rise tester of the three-phase compressor is equal.
2. How to judge the compressor motor winding short circuit?
Use a multimeter to select the resistance gear, and after zero adjustment, measure the resistance value of the compressor motor winding C-R or C-S. If the resistance value of the measured winding is less than the normal value, it can be judged that the winding is short-circuited.
Three-phase compressor:
◆ The resistance value measured 2 times is infinite, indicating that one set of windings is open;
◆ All three tests are infinite, indicating that at least two sets of windings are open;
◆ The resistance value measured in 2 of the 3 measurements is significantly lower than the other measurement, indicating that there is a short circuit.
3. How to judge that the compressor motor hits the shell and passes the ground?
Use the resistance file of the multimeter. Then put one pen tightly against the common point, and another test pen tighten the compressor process tube to expose the metal part, or take off a small piece of paint on the shell plate for measurement. If the resistance value is very small, it can be judged that the winding or the internal wiring touches the shell through the ground.
4. How to judge that the compressor motor winding is open?
Adjust the multimeter to the resistance range, connect the test leads to the terminals of any two windings, and measure the resistance value. If the winding value is infinite, that is, there is no conduction between the terminals of the two windings, it can be judged that the winding is open.
5. What to check if the compressor does not start?
◆ Check whether the compressor is overloaded, the pressure switch, and the overcurrent protector are tripped or damaged.
◆ Check the room temperature sensor and tube temperature sensor for open circuit or poor contact, and for short circuit in heating state.
◆ Check whether the relay is closed, the compressor is open or short-circuited, and the compressor capacitor is broken.
6. What are the reasons for the compressor to be overheated and stop soon after starting?
◆ The refrigerant is insufficient or excessive, the capillary assembly is blocked, and the inside of the four-way valve is leaking.
◆ The compressor itself malfunctions, such as short circuit, open circuit, contact with the shell and ground.
◆ If the high pressure pressure is too high, the pressure relay will act.
◆ The condenser is poorly ventilated or the air flow is short-circuited, or the system is mixed with non-condensable liquid gas.
◆ The ambient temperature of the outdoor unit is too high.
◆ Compressor jammed cylinder or hung shaft.
7. The performance of low compressor efficiency
Generally, the discharge pressure drops, the suction pressure rises, and the temperature of the compressor cylinder head and suction and discharge chambers is too high.
8. Judgment of the compressor's inability to work
First test whether the suction port is inhaled, and then test whether the exhaust port is exhausted, and block the exhaust port with your hand. If you feel that the pressure is not very large, or even there is no exhaust, it can be considered that the compressor has lost its working ability.
9. Why is the compressor motor too current?
There is a short circuit between the compressor turns, but the fuse is not blown. The "secondary friction" of the compressor destroys the smoothness of the friction surface, causing the compressor's power and current to increase, but it has not reached the level of "holding shaft" or "cylinder jamming", preventing the compressor from rotating.
Use a multimeter to check the insulation resistance of the compressor to the ground. Normally, it should be above 2MΩ. If it becomes smaller or close to zero, it indicates a short circuit. If the insulation resistance to ground is normal, check the resistance value of the starting and running windings. [This article is from the public number of Refrigeration Encyclopedia] If there is a short circuit between turns, the operating current increases.
10. What are the reasons for the difficulty in starting the three-phase compressor motor?
◆ The power supply voltage is too low and the compressor motor winding is short-circuited.
11. How to troubleshoot the problems that the speed of the three-phase compressor motor slows down, the fuse of one phase is blown, and the current of one phase increases during operation?
◆ It is often caused by the fact that the windings of the compressor motor are connected to the ground. After removing the ground wire, use a test pencil to test whether the case is live. If the casing is live, rewind the compressor motor winding or replace the compressor.
12. How to eliminate the "whooping" sound from the three-phase compressor motor during operation?
◆ The three-phase compressor motor emits "wheezing" during operation, which is caused by the serious imbalance of the three phases. One phase of the power supply is missing, and the three phases can be restored.
13. How to exclude the reverse rotation of the three-phase compressor motor?
◆ It is caused by wrong wiring, just change two wires of the three-phase arbitrarily.
14. Compressor replacement sequence and points of attention
◆ R22 is a non-flammable gas, but if it comes into direct contact with a high-temperature flame, it will produce toxic gas. Therefore, before welding, release the refrigerant in the refrigeration system.
◆ R32 is a flammable and explosive refrigerant. Our Refrigeration Encyclopedia has repeatedly emphasized the characteristics of this refrigerant. Any R32 refrigeration equipment involved in the maintenance of the refrigeration system requires replacement of parts, it must be vacuumed before operation! Be careful not to introduce fire sources!
◆ R410A is low-toxic, non-flammable and non-explosive. To replace the compressor, you must use the R410A compressor, and definitely not install the R22 compressor. When replacing the valve, there is a special mark on the valve body of R410A
15. What are the types of compressor overload protectors for air conditioners?
◆ External overload protector; embedded overload protector.
16. What are the protections of compressors?
◆ Overload protector: Mainly used for overcurrent and overheat protection of compressor motor.
◆ Internal protector: It mainly protects the compressor motor from overcurrent.
◆ Thermal relay: Mainly used for line overcurrent protection of three-phase compressor motors.
◆ Reverse phase preventer: Mainly used for three-phase rotary compressors to prevent the compressor from reversing the direction of rotation or lacking phase energy.
17. What are the common reasons for overload protectors?
◆ The power supply voltage is too low and the symmetry of the three-phase voltage is poor.
◆ The compressor motor runs at low speed for extended time.
◆ The compressor motor runs at low voltage for a long time with load.
◆ The cooling medium passage of the compressor motor is blocked.
◆ The operating environment temperature is too high.
18. What is the hydraulic shock of the compressor?
◆ The refrigerant does not completely evaporate in the evaporator, causing the refrigerant to be sucked back by the compressor in wet vapor or liquid form, causing liquid shock to the compressor.
◆ The hydraulic shock will cause damage to the valve disc, valve plate, and piston. In severe cases, the connecting rod may be deformed and even the compressor may be damaged.
Analysis of common failure causes of hermetic refrigeration compressors
Recent related posts
-
07/23/2020
Analysis of common failure causes of hermetic refrigeration compressors
1. How to identify the 3 terminals on the casing of a hermetic compressor?<br></br> The resistance between running terminal (R), starting terminal (S), common terminal (C), RS is greater than the resistance between SC and RC. The resistance between RS is equal to the resistance between SC and the resistance between RC.<br></br>
-
07/23/2020
FAQs about refrigeration compressors, do you know these?
Why control the impurity content and moisture content of the compressor and air conditioning system? Impurities entering the friction surface of the moving parts in the compressor pump body will cause abnormal scratches and wear. Impurities entering the solenoid valve, expansion valve, control valve, capillary tube and stop valve in the refrigerator system will block the valve hole or make the valve close tightly. And fail.
-
07/23/2020
How to reduce the discharge temperature of refrigeration compressor
The refrigeration compressor is the core and heart of the refrigeration system. The capacity and characteristics of the compressor lead to the capacity and characteristics of the refrigeration system. In a sense, the design and matching of the refrigeration system is to reflect the capacity of the compressor.
-
07/22/2020
Method for identifying failure of hermetic refrigeration compressor
The resistance between running terminal (R), starting terminal (S), common terminal (C), RS is greater than the resistance between SC and RC. The resistance between RS is equal to the resistance between SC and the resistance between RC.
-
07/22/2020
Ford Explorer air conditioner fails to refrigerate troubleshooting
Trouble phenomenon: A 2017 Ford Explorer with a mileage of about 36,000 km and a dual-zone automatic temperature control air-conditioning system. User feedback: The air conditioner has insufficient cooling during the use of the car.
-
07/22/2020
Carrier screw compressor motor repair
Carrier screw compressor motor repair<br></br> <br></br> Performance characteristics<br></br> <br></br> Use of chlorine-free refrigerant HFC-134a;<br></br> <br></br> 06N twin screw compressor achieves high full load efficiency;<br></br> <br></br> Use flooded evaporator and condenser to enhance heat exchange efficiency;<br></br> <br></br> Using electronic expansion valve, precise control;<br></br>
-
07/22/2020
The working principle of cooling and heating of air conditioning
In addition to the cooling function, the heating and cooling air conditioner also has the heating function. The biggest difference from a single-cooling air conditioner is that an electromagnetic four-way reversing valve is installed in the heating and cooling air conditioner.
-
07/22/2020
Does car air conditioner cost oil for cooling or heating? Do you really know?
The compressor of the car air conditioner is driven by the engine. Turning on the air conditioner is equivalent to increasing the engine load. Of course, it will consume more fuel. The fuel consumption of the car when the air conditioner is turned on is higher than when it is not turned on, and the fuel consumption is not increased when heating.
-
07/22/2020
Maintenance example of poor cooling effect of inverter air conditioner
Today, I will tell you about the maintenance example of the poor cooling effect of the air conditioner.<br></br> <br></br> 1. The cooling is poor, and the operating frequency is not up to the highest. The exhaust pipe overheating code will be displayed for about 20 minutes.<br></br>
-
07/22/2020
The adjustment principle of the screw compressor slide valve is actually very simple!
Today, I will tell you about the maintenance example of the poor cooling effect of the air conditioner.<br></br> <br></br> 1. The cooling is poor, and the operating frequency is not up to the highest. The exhaust pipe overheating code will be displayed for about 20 minutes.<br></br>