Probable bellows leak in KVC capacity regulator. Solution Slowly loosen protective cap. If pressure or traces of refrigerant exist under the cap,there is a leak in the bellows.Replace valve.
Hot gas quantity too large. Solution Area High pressure System Part Compressor Symptom Compressor discharge pipe too hot Potential Cause Hot gas quantity too large. Solution If necessary,set the KVC capacity regulator at lower pressure.An injedtion valve(e.g.TE2)can be installed in the suction line.