1. Insufficient oil flow, increase the oil supply appropriately;

  2, the assembly sequence of the refrigeration compressor stuffing box is unreasonable and should be assembled according to the procedure;

  3, the filler is poorly researched, it should be re-grinded;

  4. The surface of the piston rod is scratched (groove marks), which needs to be repaired (fine grinding) or replaced;

  5. The refrigeration compressor stuffing box is not well integrated (bad contact), the contact surface should be scratched again; adjust.

  6. The stuffing box is not tightened completely, and the stuffing gland should be fully tightened;

  7. The movement trajectory of the piston rod is not parallel to the center line, and the center should be adjusted;

   8. The piston rod of the refrigeration compressor sinks, replace the supporting shoe;

  9. The spring is not tightly held and should be adjusted appropriately;

   10. If the axial clearance of the packing is too large, it should be carried out according to the standard axial clearance regulations.